Technical specs for 5 kva DG  -
  Qualitative Requirement BPSL Specifications
  BPSL MODEL NO. EGD 5 LD MM1
A Genset   
  Rating  ( KVA )  5 single phase 
  Engine & alternator coupling and mounting details Taper shaft coupling , mounting on AVM's
  Fuel tank capacity  ( litres )  90
  Cont. run hrs in single fill 60
  Control Panel Voltmeter 
  Ammeter 
  Hour meter
  Fuel level gauge
  Battery charging indication
  Key start switch 
  Main ON/OFF Switch with Indication
  DG ON/OFF Switch with Indication
  Low Lub.Oil Pressure Auto shut off
   
  Battery capacity / make 55 AH
  Size ( L x W X H ) Metre 1.56X.93X1.02
  dry weight ( kgs ) 250
  CPCB Noise  norms compliance cert. No. 06121303/1.07/T-214
  Battery charging  Through charging alternator
B Engine -  
  Model/Make 15LD440, Lombardini
  Cooling  Air
  No of cyl  one
  Cycle 4 stroke diesel cycle
  Cont. power / RPM  9.3HP@ 3000RPM
  CPCB Emission norms compliance cert. No. ARAI/MOEF/DGTA/LIPL-F1/2006-030
  Fuel consumption ( lit / hr ) 1.5*
  Weight ( Kgs )  48
  Starting System electric
C Alternator  
  Model / make EK2MCT/SINCRO/MECCALTE
  Type 1 Phase,brushless
  Voltage 230 V
  Power factor unity
  RPM 3000
  Efficiency (at full load )  81.0%
  Rating 5 kva
  Voltage regulation +/- 5 %
  Weight ( Kgs )  25.9
  In case of AMF following functions will add -   
  1. Battery charging thur AMF and indication 2.Auto mains off / on with suitable safety and displays
   
  * Fuel consumption @75% load